Single-phase AC voltage drop: resistance model
Voltage drop depends on current, the complete circuit length and conductor resistance. This page explains an ohmic approximation only. It does not approve cable sizes or electrical safety.
Use the corresponding calculator with values for your product or project. This guide cannot verify local technical rules.
Open German calculator →Step-by-step guidance
1. Enter the one-way cable distance
A typical single-phase circuit contains outgoing and returning conductors. The calculation doubles the measured one-way distance internally; do not double it yourself.
2. Verify material resistance and operating temperature
Conductor resistance changes with metal type, actual cross section and temperature. The example value is not a guaranteed operating resistance for a warm or installed cable.
3. Separate numerical drop from an electrical design decision
This estimate omits reactive impedance, fault protection, current capacity and installation practices. Applicable electrical standards and qualified review still govern the circuit.
Formula
Loop resistance R = 2 × one-way length × conductor resistivity / area; voltage drop ΔV = current × R; percentage drop = 100 × ΔV / supply voltage.
Worked example
For 12 A over a 20 m one-way conductor with 2.5 mm² copper and 0.0178 Ω·mm²/m, the resistance is 0.2848 Ω. Drop is 3.4176 V, or about 1.49% of a 230 V source.
Common mistakes
- Entering the full round-trip distance and doubling it again
- Applying a copper resistivity assumption to other materials
- Treating a small voltage drop as evidence of a safe installation
Frequently asked questions
Can this select a safe cable size?
No. It cannot check protective devices, installation methods, current-carrying capacity or local electrical requirements.
Does the formula apply directly to three-phase circuits?
No. Balanced three-phase systems have different circuit relationships and can require reactive impedance terms.
Example values are planning assumptions, not binding product specifications. Check local rules, supplier information and professional guidance. Electrical examples do not establish a safe installation or protection.