Adding insulation: a simplified U-value comparison
The U-value expresses heat flow through an assembly per square metre and degree of temperature difference. If the current U-value is known, adding a homogeneous insulation layer increases thermal resistance and reduces the idealized heat-transfer coefficient. Real buildings require a complete construction and moisture assessment.
Use the corresponding calculator with values for your product or project. This guide cannot verify local technical rules.
Open German calculator →Step-by-step guidance
1. Begin with a verified existing U-value
The current U-value must represent the relevant wall or roof before new insulation. A guess based only on wall thickness can miss air layers, materials and thermal bridges.
2. Convert thickness and thermal conductivity
Divide insulation thickness in metres by the thermal conductivity in W/(m·K) to obtain additional resistance. Add that value to the inverse of the existing U-value.
3. Limit the conclusion to a comparison
The resulting theoretical U-value excludes fixings, repeating thermal bridges, moisture and construction details. Regulatory compliance and condensation risk require a professional whole-assembly evaluation.
Formula
New U-value = 1 / (1 / existing U-value + added insulation thickness (m) / conductivity (W/(m·K))).
Worked example
For an existing U-value of 1.0 W/(m²·K), 12 cm of insulation at 0.035 W/(m·K) gives roughly 0.226 W/(m²·K) in this simplified model.
Common mistakes
- Entering centimetres as metres
- Using insulation thickness without thermal conductivity
- Treating the result as an energy certificate or condensation assessment
Frequently asked questions
Why does the U-value become smaller?
Adding a thermal resistance increases total resistance; its reciprocal becomes lower.
Is the result suitable for regulatory proof?
No. It is a transparent single-layer comparison without a full building-physics model.
Example values are planning assumptions, not binding product specifications. Check local rules, supplier information and professional guidance. Electrical examples do not establish a safe installation or protection.
Related calculators