Adding insulation: a simplified U-value comparison

The U-value expresses heat flow through an assembly per square metre and degree of temperature difference. If the current U-value is known, adding a homogeneous insulation layer increases thermal resistance and reduces the idealized heat-transfer coefficient. Real buildings require a complete construction and moisture assessment.

Deutsche Originalfassung

Calculate your result

Use the corresponding calculator with values for your product or project. This guide cannot verify local technical rules.

Open German calculator →

Step-by-step guidance

1. Begin with a verified existing U-value

The current U-value must represent the relevant wall or roof before new insulation. A guess based only on wall thickness can miss air layers, materials and thermal bridges.

2. Convert thickness and thermal conductivity

Divide insulation thickness in metres by the thermal conductivity in W/(m·K) to obtain additional resistance. Add that value to the inverse of the existing U-value.

3. Limit the conclusion to a comparison

The resulting theoretical U-value excludes fixings, repeating thermal bridges, moisture and construction details. Regulatory compliance and condensation risk require a professional whole-assembly evaluation.

Formula

New U-value = 1 / (1 / existing U-value + added insulation thickness (m) / conductivity (W/(m·K))).

Worked example

For an existing U-value of 1.0 W/(m²·K), 12 cm of insulation at 0.035 W/(m·K) gives roughly 0.226 W/(m²·K) in this simplified model.

Common mistakes

  • Entering centimetres as metres
  • Using insulation thickness without thermal conductivity
  • Treating the result as an energy certificate or condensation assessment

Frequently asked questions

Why does the U-value become smaller?

Adding a thermal resistance increases total resistance; its reciprocal becomes lower.

Is the result suitable for regulatory proof?

No. It is a transparent single-layer comparison without a full building-physics model.

Example values are planning assumptions, not binding product specifications. Check local rules, supplier information and professional guidance. Electrical examples do not establish a safe installation or protection.