DC voltage drop in copper wires: length and cross-section
Even a copper wire has measurable resistance. The longer the circuit and the smaller the cross-sectional area, the greater the voltage lost when current flows. This teaching tool assumes copper at around 20 °C and does not check electrical installation safety.
Use the corresponding calculator with values for your product or project. This guide cannot verify local technical rules.
Open German calculator →Step-by-step guidance
1. Measure the one-way route
Enter the physical distance from source to load once. The current travels through an outgoing and return conductor, so the model applies a factor of two internally.
2. Apply the copper resistivity assumption
Use a conductor cross-section in square millimetres and the given approximate 20 °C resistivity. Real conductors warm up, and contact resistance may also increase circuit losses.
3. Convert resistance to voltage and power loss
Multiply loop resistance by current for the voltage drop. Relate it to the source voltage to obtain a percentage and multiply current by drop for loss power. None of these values sizes fuses or establishes current-carrying safety.
Formula
Loop R (Ω) = 2 × one-way length (m) × 0.0178 (Ω·mm²/m) / cross-section (mm²); drop (V) = I × R.
Worked example
For a 12 V source at 5 A through 10 m of 2.5 mm² copper, the simplified resistance is 0.1424 Ω and the voltage drop is 0.712 V.
Common mistakes
- Entering twice the one-way distance
- Using the copper number for aluminium
- Assuming voltage drop proves cable safety
Frequently asked questions
Is the input length already round-trip?
No. Enter the one-way physical route, because the calculator doubles it.
Can this replace an electrician’s cable calculation?
No. Temperature, protective devices, installation method and regulatory requirements must be assessed separately.
Example values are planning assumptions, not binding product specifications. Check local rules, supplier information and professional guidance. Electrical examples do not establish a safe installation or protection.